Manifold Force Mains
Source:Internet Author:Unknow Pubdate:2010-02-20  
gt5879c (Civil/Environme) 12 Oct 09 13:41
I have designed a manifold force main before. It had two pump stations on one force main. I used the graphical method where you plot the pump curves, modified pump curves and system curve for the common force main section, but I need to design one with three pumps. I don't know how to go about using the graphical method for three pump stations. Can anyone provide me with some direction? Or if you could explain the calculations so I wouldn't have to do it graphically, that would be great, too. Thanks.

jartgo (Civil/Environme) 12 Oct 09 19:14
I'll take a stab at this one.  I think you should be able to look at the problem as three separate headloss equations.

I'm going to go through the calculation for the first pump, which pumps into the force mains from the other two pumps.  
字串2


1) Determine what your flow rate needs to be.  
2) Determine what your head loss would be on the line from that pump to the point where it ties to the next forcemain (based on the flow from that pump only). At this connection point, place a check valve.
3) On the next section of force main, you will need to calculate it's head loss based on the flow from pump 1 and pump 2.  The pipe run for this section should consider only the distance from the tie-in to the point where it ties into the last forcemain.  Another check valve would be placed here.
4) On the last section of force main, you will need to calculate head loss based on the flow from all three pumps.  The pipe run for this section should consider only the distance from this tie-in point to the discharge point.  
5) The total head to be overcome is then found by adding up all the headloss from any section of pipe which the pump must pump through.  

For instance, the first pump must overcome the headloss from all three sections of force main.  The second pump must overcome the headloss from from the last two sections of force main.  The third pump must overcome the headloss from the last section of force main...keeping in mind you are calculating this headloss with all three pump flows, not just pump number three.
字串4


If this isn't clear, I can try to draw a sketch and upload it.

(Click:
Previous:Velocity for a suction hose on a self priming pump   Next:Why horizontal distance on Gravity Sewer Profiles?
[Add TO Favorites] [TOP] [PRINT] [CLOCE WINDOWS]  
  Hot Article
·How to find velocities in sani
·Maximum Slope 8" sanitary
·MECHANICAL AERATORS vs VENTURI
·Maximum Velocity PVC Pipe
·conversion chart
·specific gravity of sewage
·Technique for Calculating FLow
·sewer pump wet well sizing
·Minimum slope for effluent pip
·Splitter Box design
·Maximum force main velocity re
·Force Main inspection/cleaning
  Related Articles
·Why horizontal distance on Gra
·Force Main Comminutor Applicat
·reactor air requirements?
·PD Blower Manufacturers?
·Digester Struvite Control Stra
·Testing of water retaining str
·Nutrients recovery from sludge
·Sanitary flow rate and Fixture
·Elementry School Wastewater St
·Bigger Pipe = Less Freezing?
·Venting Interceptor Sewers
·ASME PT-9 Blower Test?
Cheap LouisVuitton Bags Civil / Environmental Engineers Structural Engineers Aeronautic Engineers Automotive Engineers Chemical Engineers Geotechnical Engineers Industrial / Manufacturing Engineers Materials Engineers Computer Engineers Agricultural Engineers Mechanical Engineers Petroleum Engineers Bioengineers Military Engineers