Fire hose flow rate
Source:Internet Author:Unknow Pubdate:2008-03-19  
dicksewerrat (Civil/Environme) 1 Feb 08 21:06
Here isa simple problem I cannot get my head around. I hav100 ft. of 2 inch fire hose. Pressure at the hydrant is 60 psi static. What will I get for a flow rate for this hose? Hose is open to atmosphere. Ia sure I have done this in the past but I feel  am missng something Richard A. Cornelius, P.E.
WWW.amlinereast.com

RWF7437 (Civil/Environme) 1 Feb 08 21:24
Usually, this problem is stated somewhat differently:

"If the residual pressure at the hydrant is allowed to fall to 20 psi what flow will be available ? "

If stated this way it is fairly simple to use both the Darcy -Weisbach equation and the Bernoulli equation to calculate the available flow at 20 psi residual pressure.

You will need to look up the friction factor (f) for the 2" hose. It is probably about 0.020. Total available head is 60 psi-20 psi or about 40psi which is equivalent to 93.6 feet of water.
字串6


The flow can be calculated by trial and error or by using a program such as EPANet2.

good luck

RWF7437 (Civil/Environme) 1 Feb 08 21:36
http://www.dcfp.navy.mil/library/tables/frictionloss.htm

Artisi (Mechanical) 2 Feb 08 15:53
Check with your local fire department, they should have tables for flowrates based on hydrant pressure / hose length.

RWF7437 (Civil/Environme) 2 Feb 08 17:29
Correction !

I should have said, "If the residual pressure at the NOZZLE is allowed to fall to 20 psi what flow will be available ? "

Using the Table provided in my previously posted link, I get a flow of about 248 gpm and a friction factor "f" of about 0.018.


字串3



CarlB (Civil/Environme) 3 Feb 08 1:11
I don't believe the 20 psi comes in to play, at the hydrant or the nozzle.  20 psi is used for establishing maximum available hydrant flow, when pumped and drawn down to 20 psi.

You really need to know the supply system characteristics to do it accurately.  If it has "unlimited" supply, then you can assume pressure remains at 60 psi when the hose is flowing.  Run the bernoulli eguation between the hydrant and the nozzle, account for hose friction loss, nozzle loss, and dynamic head at exit.  pressure at the outlet is zero.

If you have hydrant flow test data, then you include this data in the equation, as the pressure will drop some at the hydrant.

bimr (Civil/Environme) 3 Feb 08 1:48
I agree with CarlB that you have to know the supply system characteristics to do it accurately. You also must take into consideration the elevation of the hose nozzle relative to the hydrant. That elevation may account for +/- 100 feet of head.

字串4



If these factors are not taken into consideration, then you are just asking how much flow goes through a fire hose.

Artisi (Mechanical) 3 Feb 08 3:35
Go to your favourite search engine (google) and type in "calculate the flow rate for fire hose"  - or something similar - I came up with the following link - I haven't run it or even looked at it -  up to you to investigate

http://www.tucows.com/preview/279857

As I noted before - go to your local fire dept. they should have all the info you need.

riskengr (Industrial) 12 Feb 08 10:27
You can get a rough estimate by assuming that the hose will flow its maximum flowrate with no pressure left at the end of the hose.  Assuming the hydrant stays at 60-psi and you are using 100 ft of open ended 2" hose (pressure drop across the line of 60 psi) you will max out in the area of 300 - 320 GPM.  The actual flow will probably be less. Services provided include: Fire Protection Engineering, Emergency Response Planning, Fire Investigation and Process Safety Management.

字串7




dicksewerrat (Civil/Environme) 12 Feb 08 14:28
Thank you, all for your help. Richard A. Cornelius, P.E.
WWW.amlinereast.com


(Click:

Previous:HDPE Pipe Failure   Next:STEP
[Add TO Favorites] [TOP] [PRINT] [CLOCE WINDOWS]  
  Hot Article
·Langelier Index
·Galvanised Mild Steel Pipe
·HIGH CHLORIDE WASTEWATER
·Sealants & backstop water
·Pipe and Pipe Fitting Dimensio
·Selexol Solvent Process
·Is Ro plant requried - before
·Bulk Water Truck Filling Stati
·Hydraulic Grade Line Conversio
·CO2 Sparging pH Neutralization
·Pipeline isometrics
·DIP vs. HDPE?
  Related Articles
·STEP
·brass or bronze service saddle
·rural distribution system pres
·Equivalent Length
·Is anyone treating Grey Water?
·Zinc Levels higher than permit
·slope of sewer line
·Sequestering Agent for Softeni
·Stainless Steel Corrosion
·Is it a good career for struct
·WaterCAD, (Message ID 40005) P
·ALT Item for Pinch-type checkv
Power by DedeCms